Place of Origin | Germany |
Brand Name | SIEMENS |
Certification | CE |
Model Number | 6ES7516-3AN02-0AB0 |
Document | Product Brochure PDF |
SIEMENS 6ES7516-3AP03-0AB0 PROFINET IRT WITH 2-PORT SWITCH, 2ND INTERFACE: PROFINET RT, 3RD INTERFACE: PROFIBUS
The SIEMENS 6ES7516-3AP03-0AB0 is a central processing unit (CPU) that is part of the SIMATIC S7-1500 automation system. Here are the key details about this CPU:
PROFINET IRT with 2-Port Switch:
- The CPU has two PROFINET ports with an integrated 2-port switch.
- This allows the CPU to be directly connected to a PROFINET network in a line topology without requiring additional switches.
- The PROFINET interface supports the IRT (Isochronous Real-Time) protocol for highly deterministic and synchronized communication.
Second PROFINET Interface (PROFINET RT):
- In addition to the PROFINET IRT interface, the CPU also has a second PROFINET RT (Real-Time) interface.
- This provides additional network connectivity options and flexibility for the automation system.
PROFIBUS Interface:
- This CPU model is equipped with a third interface - a PROFIBUS interface.
- PROFIBUS is an industrial fieldbus protocol commonly used for connecting automation devices.
- The PROFIBUS interface allows the CPU to communicate with other PROFIBUS-enabled devices on the network.
Other Features:
- Work Memory: 1 MB for program and 5 MB for data
- Powerful CPU with high processing capabilities
- SIMATIC memory card required for operation
- Part of the modular SIMATIC S7-1500 system
- Programmed using the STEP 7 engineering software
The key distinguishing feature of this CPU model is the inclusion of the third PROFIBUS interface, in addition to the dual PROFINET interfaces. This provides extensive connectivity options and makes the CPU well-suited for applications that require integration with both PROFINET and PROFIBUS networks.
General information | ||
Product type designation | CPU 1516-3 PN/DP | |
HW functional status | FS04 | |
Firmware version | V3.1 | |
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Isochronous mode | Yes; Distributed and central; with minimum OB 6x cycle of 375 µs (distributed) and 1 ms (central) | |
● SysLog | Yes | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated from version | V19 (FW V3.1) / V18 (FW V3.0) or higher; with older TIA Portal versions configurable as 6ES7516-3AN02-0AB0 | |
Configuration control | ||
via dataset | Yes | |
Display | ||
Screen diagonal [cm] | 6.1 cm | |
Control elements | ||
Number of keys | 8 | |
Mode buttons | 2 | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
Input current | ||
Current consumption (rated value) | 0.69 A | |
Current consumption, max. | 1.08 A | |
Inrush current, max. | 1.15 A; Rated value | |
I²t | 0.6 A²·s | |
Power | ||
Infeed power to the backplane bus | 12 W | |
Power consumption from the backplane bus (balanced) | 6.7 W | |
Power loss | ||
Power loss, typ. | 4 W | |
Memory | ||
Number of slots for SIMATIC memory card | 1 | |
SIMATIC memory card required | Yes | |
Work memory | ||
● integrated (for program) | 2 Mbyte | |
● integrated (for data) | 7.5 Mbyte | |
Load memory | ||
● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte | |
Backup | ||
● maintenance-free | Yes | |
CPU processing times | ||
for bit operations, typ. | 6 ns | |
for word operations, typ. | 7 ns | |
for fixed point arithmetic, typ. | 9 ns | |
for floating point arithmetic, typ. | 37 ns | |
CPU-blocks | ||
Number of elements (total) | 8 000; Blocks (OB, FB, FC, DB) and UDTs | |
DB | ||
● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 | |
● Size, max. | 7.5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB | |
FB | ||
● Number range | 0 ... 65 535 | |
● Size, max. | 1 Mbyte | |
FC | ||
● Number range | 0 ... 65 535 | |
● Size, max. | 1 Mbyte | |
OB | ||
● Size, max. | 1 Mbyte | |
● Number of free cycle OBs | 100 | |
● Number of time alarm OBs | 20 | |
● Number of delay alarm OBs | 20 | |
● Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 250 µs | |
● Number of process alarm OBs | 50 | |
● Number of DPV1 alarm OBs | 3 | |
● Number of isochronous mode OBs | 3 | |
● Number of technology synchronous alarm OBs | 2 | |
● Number of startup OBs | 100 | |
● Number of asynchronous error OBs | 4 | |
● Number of synchronous error OBs | 2 | |